Protocol 3 Controller Owner’s Manual WORKING WITH OPERATING MODES
Version 1.2 39
Copyright © 2013 by Despatch Industries.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
a. For Segment End Type, with Control Off highlighted, press .
32. For Profile Created, press .
33. Press and to display the Main Menu. Press or to select Mode Selection
and press .
Table 13. Profile Parameter Options.
Number of profiles = 64 maximum.
Total number of segments (all programs) = 255 maximum.
1 to 9999 loops back to specified segment.
1 to 9999 or Infinite repeats per profile.
1 to 9999 or Infinite repeats of joined profile sequences.
Ramp Up/Down over time, Ramp Rate Up/Down, Step, Dwell, Hold,
Join A Profile, End or Repeat Sequence Then End.
All times specified in hh:mm:ss (Hours, Minutes & Seconds).
Maximum segment time 99:59:59 hh:mm:ss. Use loop-back for
longer segments (e.g. 24:00:00 x 100 loops = 100 days).
0.001 to 9999.9 display units per hour.
Release With Key-press, At Time Of Day or via a Digital Input.
1st segment starts from current setpoint or current PV input value.
After 0 to 99:59 (hh:mm) time delay, or at specified day(s) & time.
Note: Enable Automatic Start in the Profile Setup: General
Configuration Menu. Delayed start will not operate unless
Automatic Start has been enabled.
Selectable from: Control Off, Maintain Last Profile SP, Control
Off with Events. Use Controller Setpoint or Control Outputs Off.
Selectable from: Keep Last Profile Setpoint, Use Controller Setpoint
or Control Outputs Off.
Power/signal Loss
Recovery Action
Selectable from: Continue Profile, Restart Profile, Keep Last Profile
Setpoint, Use Controller Setpoint or Control Outputs Off.
Off or Hold if input >Band above and/or below SP for each
segment.
Run, Manual Hold/Release, Abort or jump to next segment.
0.02% Basic Profile Timing Accuracy.
± <0.5 second per Loop, End or Join segment.
Events turn on for the duration of the segment. For End Segments,
the event state persists until another profile starts, the user exits
from profiler mode, or the unit is powered down.