Optional decimal place can be displayed up to 999.9°C/F
Thermocouple
Calibration:
±0.1% of full range, ±1LSD (±1°C for internal CJC if enabled).
Linearization better than better ±0.2°C (±0.05 typical) on
ranges marked * in the table above. Linearization for other
ranges is better than ±0.5°C. BS4937, NBS125 & IEC584.
Supported RTD Types
& Ranges:
Optional decimal place can be displayed up to 999.9°C/F
0.1% of full range, ±1LSD
Linearization better than ±0.2°C (±0.05 typical).
PT100 input to BS1904 & DIN43760 (0.00385Ω/Ω/°C).
Sensor current 150μA ±10%
<0.5% of span error for max 50Ωper lead, balanced
Supported Linear
Types & Ranges:
Scalable from ‐9999 to 10000. Decimal point selectable from 0
to 3 places, but limited to 5 display digits (e.g. 9999.9)
1A on mA input terminals, 30V on voltage input terminals
±0.1% of full range, ±1LSD
DC Input Multi‐Point:
Linearization:
Up to 15 scaling values can be defined anywhere between 0.1
and 100% of input
Table 2. Outputs.
Single pole single throw (SPST); 2A resistive at 120/240VAC
>200,000 operations at rated voltage/current